Positive and Zero Sequence impedance for Line

       132kV Substation-B is being feed by 132kV single circuit radial line A-B having line length   km. Line +Ve sequence impedance is 0.16+J0.40 ohms/km. Source Substation-A has 132kV Bus 3-Ph fault level as  MVA. Its 1-Ph fault level is  MVA. Find out the Substation-B 132kV Bus fault current for 1-Ph to ground fault (SLG).
(Note: Consider line zero sequence impedance as 3 times +Ve sequence impedance; and Base MVA as 100).
1) 3-Ph Fault MVA = BaseMVAx100/X1S; Thus: X1S=    %
2) As 1-Ph Fault MVA = 3xBaseMVAx100/(X1S+X2S+X0S);
Source Substation-A X1S+X2S+X0S =   %
3) As X1S = X2S and from 1 and 2 we can have X0S =   %
4a) For  km line ohmic reactance =   Ohms

4b) and its +Ve Seq. % reactance =   %
5) For Line X0L =  %
6a) Equivalent sequence impedance will be X1 = X1S + X1L =  %
6b) X2 = X2S + X2L =  %
6c) X0 = X0S + X0L =  %
7) X1 + X2 + X0 =    %.
8) Thus for Substation-B SLG Fault MVA =   MVA.
9) Substation-B SLG Fault Current =   AMP.
Topic FLTCALC Ex-4 Your score is:
Select Zone:
Select Unit:
Code Number:

No comments:

Post a Comment